DocumentCode :
1315617
Title :
The distribution of lightning strokes to towers and along the span of shielded and unshielded power lines
Author :
Mousa, A.M. ; Srivastava, K.D.
Author_Institution :
British Columbia Hydro, Vancouver, BC, USA
Volume :
15
Issue :
3
fYear :
1990
Firstpage :
115
Lastpage :
122
Abstract :
A knowledge of the distribution of lightning strokes to towers and along the span of shielded power lines is needed to refine the outage rate calculation method. Such information is also needed for unshielded line because the outage mechanism differs depending on whether the stroke terminates on a tower or on a live wire. The authors provide the needed information based on a 3-D representation of the line and on a validated revised electrogeometric model. The effects of height, span and width of tower are studied and the span is found to be the most important governing parameter. Unshielded lines are found to have similar characteristics except that the tower collects a larger percentage of the total strokes and its shielding influence on adjacent wire segments is more pronounced. The effects of the form of striking distance equation and the coefficient of striking distance to the tower are also investigated.
Keywords :
lightning; poles and towers; power overhead lines; shielding; 3D line representation; electrogeometric model; lightning strokes distribution; outage mechanism; power cable span; shielded power lines; striking distance equation; tower height; unshielded power lines; Distribution functions; Equations; Graphical models; Lightning; Mathematical model; Poles and towers; Wires;
fLanguage :
English
Journal_Title :
Electrical and Computer Engineering, Canadian Journal of
Publisher :
ieee
ISSN :
0840-8688
Type :
jour
DOI :
10.1109/CJECE.1990.6591469
Filename :
6591469
Link To Document :