DocumentCode
1316280
Title
Fast assessment methods for voltage sags in distribution systems
Author
Bollen, Math H J
Author_Institution
Centre for Electr. Energy, Univ. of Manchester Inst. of Sci. & Technol., UK
Volume
32
Issue
6
fYear
1996
Firstpage
1414
Lastpage
1423
Abstract
Based on a simple voltage divider model, a relation is derived between the load sensitivity to voltage sags (expressed as a critical voltage) and the exposed area (expressed as a critical distance). The critical distance increases about linearly with voltage level. The relation found is remarkably similar to relations found in power quality surveys. An equivalent expression is found for the critical distance as a function of the critical phase-angle jump. Realizing that faults downstream of a transformer do not significantly influence the expected number of sags, it is possible to estimate the number of sags at a specific load location. The method is extended to some nonradial systems: simple subtransmission loops, local generation, feeding from two substations, and operating with a normally open breaker
Keywords
distribution networks; fault location; power supply quality; assessment methods; critical distance; critical phase-angle jump; critical voltage; distribution systems; faults; local generation; nonradial systems; normally open breaker operation; power quality; substations; subtransmission loops; voltage divider model; voltage sags; Circuit faults; Distributed power generation; Fault diagnosis; Impedance; Industry Applications Society; Power generation; Power quality; Power system modeling; Power system reliability; Voltage fluctuations;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.556647
Filename
556647
Link To Document