DocumentCode :
1321522
Title :
Advanced partial discharge diagnostic of MV power cable system using oscillating wave test system
Author :
Gulski, Edward ; Wester, Frank J. ; Smit, Johan J. ; Seitz, Paul N. ; Turner, Mark
Author_Institution :
Delft Univ. of Technol., Netherlands
Volume :
16
Issue :
2
fYear :
2000
Firstpage :
17
Lastpage :
25
Abstract :
To obtain a sensitive picture of discharging faults in power cables the PD should be ignited, detected, and located at power frequencies that are comparable to operating conditions at 50 or 60 Hz. In this way, realistic magnitudes in [pC] and reproducible patterns of discharges in a power cable can be obtained. PD measurements during service as well as on-site continuous energizing at 50 (60) Hz of MV cables are not always economically realistic for on-site inspections. Different energizing methods have been introduced and employed during recent years. Therefore, based on the assumption that sensitive detection of critical PD sites occurs by a method mostly similar to 50 Hz energizing conditions, a method as introduced for on-site PD diagnosis of MV cables is discussed: oscillating wave test system (OWTS).
Keywords :
fault diagnosis; partial discharges; power cable insulation; power cable testing; 50 Hz; 60 Hz; MV power cable system; discharging faults; energizing conditions; operating conditions; oscillating wave test system; partial discharge diagnostic; power frequencies; reproducible patterns; Capacitance; Circuits; Frequency; Inductors; Oil filled cables; Power cables; Power supplies; Switches; System testing; Voltage;
fLanguage :
English
Journal_Title :
Electrical Insulation Magazine, IEEE
Publisher :
ieee
ISSN :
0883-7554
Type :
jour
DOI :
10.1109/57.833657
Filename :
833657
Link To Document :
بازگشت