DocumentCode :
132283
Title :
Automatic analysis of pole mounted auto-recloser data for fault prognosis to mitigate customer supply interruptions
Author :
Xiaoyu Wang ; Strachan, Scott ; Kirkwood, John ; McArthur, Stephen
fYear :
2014
fDate :
2-5 Sept. 2014
Firstpage :
1
Lastpage :
6
Abstract :
Historically restoration switching strategies have been deployed to improve the system reliability by addressing effects resulting from permanent fault activity via distribution automation schemes. This paper investigates the potential role of a Distribution Automation System (DAS) in dealing with nuisance tripping where customers are often disturbed by frequently occurring short-term supply outages affecting their quality of supply. In order to mitigate these nuisance supply interruptions, this paper will focus on the development of an integrated decision support system that utilises available Supervisory Control And Data Acquisition (SCADA) alarm data and distribution network data available from pole mounted auto-reclosers (provided by a distribution network operator) to detect and diagnose pre-permanent fault activity responsible for nuisance tripping. The developed system will detect the advent of nuisance tripping on a circuit, and subsequently conduct prognostic health checks to determine the cause of the underlying circuit fault activity, responsible for the nuisance tripping, which often leads to more serious permanent faults in the future. Previous fault activity could be used to identify fault signature data patterns and trends through data mining techniques that predict potential nuisance tripping associated with network behaviour, transient activity and permanent network faults. The distribution automation scheme may be subsequently operated to mitigate the risk of nuisance tripping and so improve the level of customer service associated with network operators. This system is capable of providing `early warning´ of evolving faults which in turn allows an intervention to take place to inform and assist maintenance staff to take appropriate preventative action to minimise negative effect prior to it occurring.
Keywords :
SCADA systems; control engineering computing; data mining; decision support systems; fault diagnosis; power distribution faults; power distribution reliability; power system analysis computing; DAS; SCADA alarm data; SCADA distribution network data; automatic pole mounted auto recloser data analysis; circuit fault activity; customer service level improvement; customer supply interruption mitigation; data mining techniques; distribution automation system; fault prognosis; fault signature data pattern identification; integrated decision support system; network behaviour; permanent network faults; potential nuisance tripping prediction; pre permanent fault activity detection; pre permanent fault activity diagnosis; prognostic health checks; restoration switching strategies; short-term supply outages; supervisory control-and-data acquisition; supply quality; system reliability improvement; transient activity; Automation; Circuit faults; Data mining; Fault diagnosis; Market research; Prognostics and health management; Transient analysis; Auto-recloser; Data mining; Decision support system; Distribution automation; Nuisance tripping; Pre-fault activity; Prognostic;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Conference (UPEC), 2014 49th International Universities
Conference_Location :
Cluj-Napoca
Print_ISBN :
978-1-4799-6556-4
Type :
conf
DOI :
10.1109/UPEC.2014.6934653
Filename :
6934653
Link To Document :
بازگشت