• DocumentCode
    132317
  • Title

    FDTD analysis using constant parameter modeling for the calculation of transient responses and voltage profiles on multiconductor overhead transmission lines

  • Author

    Kaloudas, C.G. ; Papagiannis, Grigoris K.

  • Author_Institution
    Sch. of Electr. & Comput. Eng., Aristotle Univ. of Thessaloniki, Thessaloniki, Greece
  • fYear
    2014
  • fDate
    2-5 Sept. 2014
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    FDTD models have been used since many years for the calculation of transients in overhead transmission lines (OHTLs), modeling them either as lossless or with frequency dependent parameters. Their major drawback, especially in the latter case, is their high computational cost. But FDTD models allow also the efficient calculation of voltage distributions with high discretization along OHTLs. This is significant in tracing transient overvoltages in short line segments in HV substations and in the calculation of signal voltage levels along transmission lines in Power Line Communication applications. Modal domain and phase domain frequency dependent transmission line models can provide accurate transient responses. However, when they are used in multi-segment configurations for the calculation of voltage distribution along transmission lines they may lead to error accumulations, combined with other limitations due to computational requirements or to the approaches in modal or phase domain analysis. In this paper, a constant parameter FDTD model for OHTLs is formulated, incorporating losses due to skin-effect and to the imperfect earth, capable to handle properly also non-homogeneous propagation. The proposed formulation is successfully checked against frequency dependent line models of the ATP/EMTP software, as well as against a formulated frequency dependent FDTD model. The proposed FDTD model proves to be numerically stable and is efficiently applied in voltage profile calculations.
  • Keywords
    finite difference time-domain analysis; multiconductor transmission lines; overhead line conductors; power system transients; FDTD analysis; constant parameter FDTD model; constant parameter model; high voltage substations; multiconductor overhead transmission lines; nonhomogeneous propagation; power line communication applications; signal voltage level calculation; transient overvoltage; transient response calculation; voltage profiles; Computational modeling; Earth; Finite difference methods; Numerical models; Time-domain analysis; Transient analysis; FDTD; constant parameter model; non-homogeneous propagation; overhead transmission lines; voltage profiles;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Conference (UPEC), 2014 49th International Universities
  • Conference_Location
    Cluj-Napoca
  • Print_ISBN
    978-1-4799-6556-4
  • Type

    conf

  • DOI
    10.1109/UPEC.2014.6934671
  • Filename
    6934671