Title :
New setting of loss of excitation protection in P-Q plan in order to maximize the operation area of the capacity curve of the synchronous machine
Author :
Gazen, Yuri Neves ; Bubolz Zarnott, Alexandre ; Peres de Morais, Adriano ; Cardoso, Ghendy ; de Lima Oliveira, Aecio
Author_Institution :
Companhia Estadual de Energia Eletr., Brazil
Abstract :
This paper presents a method for maximizing the operation area of the capacity curve of a synchronous machine. The technique is set in P-Q plan in order to adjust more features of minimum excitation and practical stability limits of the capacity curve. Thus, the voltage limiter can be intended to the left of the capacity curve and so the machine may have an operating gain in this region. The new setting is done primarily on the generator capacity curve, plan P-Q, and subsequently analyzed in the R-X plan.
Keywords :
machine protection; synchronous machines; P-Q plan; R-X plan; excitation protection loss; generator capacity curve; synchronous machine; Capacity planning; Impedance; Loading; Relays; Synchronous generators; Capacity Curve; Loss of Field Protection; Minimum Excitation Limit; Synchronous Generator;
Conference_Titel :
Power Engineering Conference (UPEC), 2014 49th International Universities
Conference_Location :
Cluj-Napoca
Print_ISBN :
978-1-4799-6556-4
DOI :
10.1109/UPEC.2014.6934771