• DocumentCode
    1326048
  • Title

    PD detection and localisation by acoustic measurements in an oil-filled transformer

  • Author

    Lu, Y. ; Tan, X. ; Hu, X.

  • Author_Institution
    Dept. of Electr. Eng., Southeast Univ., Nanjing, China
  • Volume
    147
  • Issue
    2
  • fYear
    2000
  • fDate
    3/1/2000 12:00:00 AM
  • Firstpage
    81
  • Lastpage
    85
  • Abstract
    A pattern recognition method for localisation of the partial discharge (PD) site in an oil-filled transformer by acoustic measurements is presented. By dividing the transformer into a number of 20×20×20 mm3 sub-modules, the PD site is localised by comparing the spatial distance of each sub-module to the acoustic sensors. The numerical cases indicate that the proposed method is general and practical, while avoiding some drawbacks in current algorithms. Moreover, the method improves the accuracy of localisation substantially when compared with the conventional localisation method
  • Keywords
    acoustic signal processing; insulation testing; partial discharge measurement; pattern recognition; power transformer insulation; transformer oil; PD detection; PD localisation; acoustic measurements; direct-path wave propagation; oil-filled transformer; pattern recognition method; sub-module spatial distance; time delay; wavelet transform;
  • fLanguage
    English
  • Journal_Title
    Science, Measurement and Technology, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2344
  • Type

    jour

  • DOI
    10.1049/ip-smt:20000223
  • Filename
    838820