• DocumentCode
    1327048
  • Title

    PD pattern analysis during induced test of large power transformers

  • Author

    Gulski, Edward ; Burger, Hendrik P. ; Vaillancourt, George H. ; Brooks, Roger

  • Author_Institution
    High Voltage Lab., Delft Univ. of Technol., Netherlands
  • Volume
    7
  • Issue
    1
  • fYear
    2000
  • fDate
    2/1/2000 12:00:00 AM
  • Firstpage
    95
  • Lastpage
    101
  • Abstract
    The partial discharge (PD) measurements on power transformers are studied with a view toward discrimination and classification of different discharge sources. For this purpose digital analysis is applied to power transformers and reactors going through acceptance testing. Furthermore, based on these measurements, PD databases have been developed to support the discharge evaluation during induced voltage tests of transformers. Using this technique, a clear distinction is possible between transformers showing different discharge behavior
  • Keywords
    insulation testing; partial discharge measurement; power transformer insulation; power transformer testing; PD pattern analysis; acceptance testing; classification; digital analysis; discharge behavior; discharge evaluation; discharge sources; discrimination; induced voltage tests; power transformers; Databases; Electrodes; Fault location; Laboratories; Partial discharge measurement; Partial discharges; Pattern analysis; Power transformers; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/94.839346
  • Filename
    839346