DocumentCode :
1328817
Title :
A nonpilot phase selector based on superimposed components for protection of double circuit lines
Author :
Jones, M.S. ; Thomas, D.W.P. ; Christopoulos, C.
Author_Institution :
GEC Alsthom T&D Protection & Control Ltd., Stafford, UK
Volume :
12
Issue :
4
fYear :
1997
fDate :
10/1/1997 12:00:00 AM
Firstpage :
1439
Lastpage :
1444
Abstract :
This paper gives details of a new phase-selection scheme for simultaneous phase-ground faults on both circuits of double circuit EHV transmission lines. Fast phase selection (within half a cycle) can be achieved by using the information contained within the fault transients. The theory is presented along with results obtained through simulations using EMTP. The scheme enables single pole tripping to be employed for simultaneous faults. The proposed scheme does not require communication between the two ends of the line. Limitations due to the low bandwidth of CVTs have not caused problems and the method has shown immunity to system noise
Keywords :
electrical faults; power system protection; power transmission lines; EMTP simulations; double circuit EHV transmission lines; double circuit lines protection; fast phase selection; fault transients; low bandwidth; nonpilot phase selector; phase-selection scheme; simultaneous phase-ground faults; single pole tripping; superimposed components; system noise immunity; Bandwidth; Circuit faults; Fault location; Power system relaying; Power system transients; Power transmission lines; Protection; Transducers; Transmission line matrix methods; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.634158
Filename :
634158
Link To Document :
بازگشت