DocumentCode :
1329086
Title :
A procedure for derating a substation transformer in the presence of widespread electric vehicle battery charging
Author :
Staats, P.T. ; Grady, W.M. ; Arapostathis, A. ; Thallam, R.S.
Author_Institution :
Texas Univ., Austin, TX, USA
Volume :
12
Issue :
4
fYear :
1997
fDate :
10/1/1997 12:00:00 AM
Firstpage :
1562
Lastpage :
1568
Abstract :
This paper studies the effect of electric vehicle (EV) battery charging on a substation transformer that supplies commercial, residential, industrial, and EV load on a peak summer day. The analysis begins by modeling non-EV load with typical utility load shapes. EV load is modeled using the results from an analytical solution technique that predicts the net power and harmonic currents generated by a group of EV battery chargers. We evaluate the amount of transformer derating by maintaining constant daily transformer loss-of-life, with and without EV charging. This analysis shows that the time of day and the length of time during which the EVs begin charging are critical in determining the amount of transformer derating required. Our results show that with proper control, EV charging may have very little effect on power system components at the substation level
Keywords :
battery chargers; electric vehicles; load (electric); power system harmonics; transformer substations; daily transformer loss-of-life; electric vehicle battery charging; electric vehicle load modeling; harmonic currents prediction; net power prediction; peak summer day; power system components; substation transformer derating; utility load shapes; Batteries; Electric vehicles; Electrical equipment industry; Harmonic analysis; Load modeling; Power generation; Power system harmonics; Predictive models; Shape; Substations;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.634176
Filename :
634176
Link To Document :
بازگشت