Abstract :
This paper deals with EDF Research and Development work for ERDF needs in terms of energy efficiency, focused on Amorphous Metal Distribution Transformers (AMDT). Many prototypes built on Metglas 2605SA1, rated 250 to 630 kVA from different manufacturers, were tested under short-circuit conditions according to IEC and ERDF standards. Some of the prototypes exceeded the accepted value of 4% of impedance variation after short-circuit test. Rectangular windings offer poor resistance to short-circuit stresses. Small metal particles, detached from amorphous core, were found at the bottom of the tank. In that case, dielectric strength is not gifted. The results show the active part should be strong enough to support high electrodynamic forces produced during short-circuit test.
Keywords :
IEC standards; power transformer testing; short-circuit currents; -circuit stresses; ERDF standard; IEC standard; Metglas 2605SA1; amorphous metal distribution transformers; electrodynamic forces; short-circuit withstand tests; Electrodynamics; Force; Power transformer insulation; Prototypes; Transformer cores; Windings; Amorphous transformers; short-circuit withstand;
fLanguage :
English
Journal_Title :
Magnetics, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9464
Type :
jour
DOI :
10.1109/TMAG.2011.2155632
Filename :
6028095
Link To Document :
بازگشت