DocumentCode
1331991
Title
Calculation of optimum directional overcurrent relays settings: the parallel lines case
Author
Perez, Luis G. ; Urdaneta, Alberto J.
Author_Institution
Simon Bolivar Univ., Caracas, Venezuela
Volume
20
Issue
5
fYear
2000
fDate
5/1/2000 12:00:00 AM
Firstpage
68
Lastpage
69
Abstract
A simple and practical criterion is proposed to consider the transient changes due to nonsimultaneous operation of directional overcurrent relays in parallel lines. The criterion consists of using two different time coordination intervals: one for relay coordination pairs that do not belong to parallel lines and another for pairs belonging to parallel lines. The method can be implemented in programs that use the optimization technique for the calculation of relay settings. Numerical results showing the performance of the method are also presented
Keywords
overcurrent protection; power system protection; power system transients; relay protection; nonsimultaneous operation; optimum directional overcurrent relays settings; parallel lines; relay coordination; relay coordination pairs; time coordination intervals; transient changes; Batteries; Capacitors; Computer aided software engineering; Energy storage; Flywheels; Lakes; Protective relaying; Relays; Samarium; Tires;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/39.841356
Filename
841356