DocumentCode :
1332326
Title :
Analysis of Transient Overvoltage in 220 kV Saturated Core HTS FCL
Author :
Hongli Xiao ; Jie Qiu ; Shuhong Wang ; Qiuhui Zhang ; WeiZhi Gong ; Ying Xin ; Jian Guo Zhu ; Youguang Guo
Author_Institution :
State Key Lab. of Electr. Insulation & Power Equip., Xi´an Jiaotong Univ., Xi´an, China
Volume :
47
Issue :
10
fYear :
2011
Firstpage :
2620
Lastpage :
2623
Abstract :
Saturated Core High Temperature Superconducting (HTS) Fault Current Limiter (FCL) is one kind of limiters that can work effectively on short-circuit current limitation. In this paper, an equivalent circuit model depending on ac coil of HTS FCL is built for voltage distribution analysis under transient overvoltage. The equivalent circuit components, such as the capacitances and inductances, are calculated by using finite element method. The voltage distribution and oscillation analysis of ac coil may benefit to the insulation design of HTS FCL.
Keywords :
capacitance; coils; equivalent circuits; finite element analysis; high-temperature superconductors; inductance; integrated circuit modelling; oscillations; short-circuit currents; superconducting fault current limiters; transients; voltage distribution; AC coil; capacitance; equivalent circuit model; fault current limiter; finite element method; inductance; oscillation analysis; saturated core HTS FCL; saturated core high temperature superconducting; short-circuit current limitation; transient overvoltage; voltage 220 kV; voltage distribution; Capacitance; Coils; Electric potential; High temperature superconductors; Lightning; Transient analysis; Voltage control; High Temperature Superconducting Fault Current Limiter (HTS FCL); lightning impulse voltage; transient overvoltage;
fLanguage :
English
Journal_Title :
Magnetics, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9464
Type :
jour
DOI :
10.1109/TMAG.2011.2158575
Filename :
6028205
Link To Document :
بازگشت