DocumentCode :
1333003
Title :
Ion mobility spectrometry for on-site sensing of SF6 decomposition
Author :
Soppart, O. ; Pilzecker, P. ; Baumbach, J.I. ; Klockow, D. ; Trindade, E.
Author_Institution :
G.A.S. Gesellschaft fur Analytische Sensorsysteme mbH, Dortmund, Germany
Volume :
7
Issue :
2
fYear :
2000
fDate :
4/1/2000 12:00:00 AM
Firstpage :
229
Lastpage :
233
Abstract :
Although gas-insulated system (GIS) and substations belong to the most reliable components of electric power networks, failures still occur in their long-term operation. In order to estimate the probability of malfunctions in advance, a system for monitoring the quality of the insulating gas SF6 was established, which is based on the use of ion mobility spectrometry (IMS). In a set of experiments, partial discharge (PD) was generated inside a test GIS. The SF6 was periodically analyzed using IMS. The results of this analysis is presented and the influence of impurities remaining inside the compartment is discussed. The analysis of gas contained in a circuit breaker in a hydroelectric power plant before and after operation is described as well as the structure of a system for automatic on-site sensing of SF6 decomposition
Keywords :
SF6 insulation; gas insulated substations; gas insulated switchgear; insulation testing; ion mobility; partial discharges; SF6; automatic on-site sensing; circuit breaker; electric power networks; gas-insulated substations; gas-insulated system; hydroelectric power plant; ion mobility spectrometry; long-term operation; partial discharge; quality monitoring; Circuit testing; Condition monitoring; Gas insulation; Geographic Information Systems; Hydroelectric power generation; Impurities; Partial discharges; Power system reliability; Spectroscopy; Substations;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/94.841814
Filename :
841814
Link To Document :
بازگشت