DocumentCode
1338247
Title
Analysis of Corona Onset Electric Field Considering the Effect of Space Charges
Author
Lu, Tiebing ; Xiong, Gaolin ; Cui, Xiang ; Rao, Hong ; Wang, Qi
Author_Institution
Sch. of Electr. & Electron. Eng., North China Electr. Power Univ., Beijing, China
Volume
47
Issue
5
fYear
2011
fDate
5/1/2011 12:00:00 AM
Firstpage
1390
Lastpage
1393
Abstract
A modified method based on the optimized charge simulation method (CSM) is used to predict the corona onset voltage and electric field when the space charges due to the corona are considered. Based on the streamer model of corona discharge, space charges generated near the conductors are predicted. In order to calculate the electric field at the conductor surface, space charges are replaced by some equivalent line charges near the conductor. Because of the existence of space charges, the corona onset electric field is changed a little. After a simplified model of actual power transmission lines is introduced with the help of rough coefficient, the corona onset voltage and corona onset electric field are calculated for different types of conductors finally.
Keywords
corona; plasma simulation; plasma transport processes; space charge; corona discharge; corona onset electric field analysis; corona onset voltage field; optimized charge simulation method; power transmission line; rough coefficient; space charge effect; streamer model; Conductors; Corona; Discharges; Electric fields; Power transmission lines; Space charge; Wires; Corona; electric field; space charge; transmission lines;
fLanguage
English
Journal_Title
Magnetics, IEEE Transactions on
Publisher
ieee
ISSN
0018-9464
Type
jour
DOI
10.1109/TMAG.2010.2081972
Filename
5587896
Link To Document