Title :
Study on a field data of secondary arc extinction time for large-sized transmission lines
Author :
Tsuboi, Toshihiro ; Takami, J. ; Okabe, Shigemitsu ; Aoki, Kazuo ; Yamagata, Yoshiki
Author_Institution :
R&D Center, Tokyo Electr. Power Co., Yokohama, Japan
Abstract :
Secondary arc extinction time is an important factor, which influences system stability because it directly affects the reclosing time. However, few reports exist on a field data of the secondary arc extinction time on transmission lines. This paper describes the investigation results of secondary arc extinction characteristics by analyzing voltage wave shapes during the lightning faults on 550 kV transmission lines. Recovery voltages and secondary arc currents on each transmission line during faults were calculated to consider correlation with the secondary arc extinction time. The secondary arc extinction time is estimated by the existing formula, the secondary arc current and the recovery voltage required for one second reclosing are evaluated.
Keywords :
arcs (electric); lightning; power system stability; power transmission faults; power transmission lines; large-sized transmission lines; lightning faults; reclosing time; recovery voltages; secondary arc currents; secondary arc extinction time; system stability; voltage 550 kV; voltage wave shapes; Circuit breakers; Circuit faults; Fault currents; Lightning; Power transmission lines; Shape; Transmission line measurements; Lightning fault; primary fault current; reclosing time; recovery voltage; secondary arc current; secondary arc extinction time;