A perspective of low-voltage circuit breaker interrupting rating
Author
Valentine, Raymond D.
Volume
36
Issue
3
fYear
2000
Firstpage
916
Lastpage
919
Abstract
This paper reviews application of all three types of low-voltage circuit breakers for three-phase fault interrupting duty by reference to the circuit breaker´s interrupting requirement and rating. After a discussion of the rating process for circuit breaker design and the fault-current evaluation process for circuit breaker application, it then considers the effect of the erroneous assumption that the load-side bolted fault interrupting let-through current of all circuit breakers is equal to the calculated line-side prospective fault current
Keywords
circuit breakers; fault currents; fault-current evaluation; insulated case circuit breakers; line-side prospective fault current; load-side bolted fault interrupting let-through current; low-voltage circuit breaker interrupting rating; low-voltage circuit breakers; molded case circuit breakers; power circuit breaker; three-phase fault interrupting duty; Circuit breakers; Circuit faults; Circuit testing; Conducting materials; Conductors; Fault currents; Performance evaluation; Protection; Voltage; Wire;