Abstract
Results and assessment are provided from a nearly 10 year study of the application of a variety of diagnostic methods applied to the condition monitoring of generator stator insulation. The methods studied included various forms of Partial Discharge (PD) techniques and Electromagnetic Interference (EMI) in the frequency domain. The condition of a number of operating machines was tracked by the various techniques and, in most cases, the findings compared with the actual condition determined by subsequent inspection after the rotors had been removed. This has permitted the effectiveness of the various methods to be gauged and allowed an appraisal of the attendant best practices and pitfalls.
Keywords
condition monitoring; electric generators; electromagnetic interference; inspection; machine insulation; partial discharges; condition monitoring; diagnostic methods; electromagnetic interference; generator stator insulation; inspection; partial discharge; Couplers; Discharges; Electromagnetic interference; Generators; Noise; Partial discharges; Stators; Partial Discharge, Electromagnetic Interference, generator insulation; stator bar, condition monitoring, high-voltage coupler, diagnostics;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2010.5595543
Filename
5595543
Link To Document