• DocumentCode
    1347896
  • Title

    An experimental thermal siphon bushing

  • Author

    Zeng, Daxiong

  • Author_Institution
    Lapp Insulator Co., LeRoy, NY, USA
  • Volume
    15
  • Issue
    1
  • fYear
    2000
  • fDate
    1/1/2000 12:00:00 AM
  • Firstpage
    175
  • Lastpage
    177
  • Abstract
    An experimental thermal siphon bushing was constructed and tested. The thermal siphon was made from the hollow conductor of a paper-resin bushing with water as heat transport fluid. The test shows that this bushing has almost uniform temperature distribution under its critical current and the temperature of its hottest spot is close to the boiling temperature of water. The current carrying capacity of this thermal siphon bushing is 50% more than that of the same bushing without thermal siphon. Simple formulas are proposed to determine the critical current of a thermal siphon bushing and estimate the temperature of the hottest spot if the bushing with thermal siphon is operated above the nameplate rating
  • Keywords
    bushings; condensation; conductors (electric); cooling; evaporation; paper; polymers; temperature distribution; 1200 A; 350 kV; condensation; critical current; current carrying capacity; evaporation; heat transport fluid; hollow conductor; hottest spot temperature; paper-resin bushing; thermal siphon bushing; uniform temperature distribution; water; Conductors; Cooling; Copper; Critical current; Insulators; Petroleum; Temperature distribution; Testing; Thermal conductivity; Water heating;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.847247
  • Filename
    847247