Comparison of fault currents in multiterminal HVDC grids with different grounding schemes
Author
Bucher, Matthias K. ; Franck, Christian
Author_Institution
Power Syst. & High Voltage Labs., ETH Zurich, Zurich, Switzerland
fYear
2014
fDate
27-31 July 2014
Firstpage
1
Lastpage
5
Abstract
The requirements of dc circuit breakers used to protect multiterminal HVDC networks are specified by the prospective fault current. The fault current, however, strongly depends on the grounding scheme of the network. Low-ohmic and high-impedance earthing practices with different grounding points are presented and compared with each other in terms of fault currents and overvoltages during a pole-to-ground fault. To do so, monopolar and bipolar configurations of a multiterminal HVDC cable network are implemented in PSCAD and simulations are performed.
Keywords
HVDC power transmission; circuit breakers; earthing; fault currents; power grids; power transmission faults; power transmission protection; PSCAD; bipolar configuration; dc circuit breakers; fault currents; grounding points; grounding schemes; high-impedance earthing practice; low-ohmic earthing practice; monopolar configuration; multiterminal HVDC cable network; multiterminal HVDC grids; pole-to-ground fault; Capacitors; Circuit faults; Fault currents; Grounding; HVDC transmission; Inductors; Surges; HVDC transmission; PSCAD; Power system faults; Power system simulation;
fLanguage
English
Publisher
ieee
Conference_Titel
PES General Meeting | Conference & Exposition, 2014 IEEE
Conference_Location
National Harbor, MD
Type
conf
DOI
10.1109/PESGM.2014.6938990
Filename
6938990
Link To Document