Title :
A survey of neutral currents in three-phase computer power systems
Author :
Gruzs, Thomas M.
Author_Institution :
Liebert Corp., Columbus, OH, USA
Abstract :
It is shown that the magnitude of the neutral current in three-phase computer power systems depends on the harmonic content and phase balance of the load currents. While very high neutral currents are possible due to the additive nature of triplen harmonic currents, a low percentage of data processing sites in the United States are actually experiencing neutral currents in excess of the rated phase current. However, trends in computer systems make high harmonic neutral currents more likely. Power system problems associated with high harmonic neutral currents include overloaded transformers, voltage distortion, and common mode noise. Whenever three-phase, four-wire power systems are used to supply power to computer systems or other similar electronic loads, the power system design should allow for the possibility of high harmonic neutral current to avoid potential problems
Keywords :
harmonics; power supplies to apparatus; United States; common mode noise; data processing sites; four-wire power systems; harmonic content; load currents; neutral currents; overloaded transformers; phase balance; three-phase computer power systems; voltage distortion; Circuits; Current supplies; Frequency; Industrial power systems; Power supplies; Power system harmonics; Power system measurements; Power systems; Rectifiers; Switched-mode power supply;
Journal_Title :
Industry Applications, IEEE Transactions on