Nondetection Zone Assessment of an Active Islanding Detection Method and its Experimental Evaluation
Author
Bahrani, Behrooz ; Karimi, Houshang ; Iravani, Reza
Author_Institution
Eng. Sch., Ecole Polytech. Fed. de Lausanne, Lausanne, Switzerland
Volume
26
Issue
2
fYear
2011
fDate
4/1/2011 12:00:00 AM
Firstpage
517
Lastpage
525
Abstract
This paper analytically determines the nondetection zone (NDZ) of an active islanding detection method, and proposes a solution to obviate the NDZ. The method actively injects a negative-sequence current through the interface voltage-sourced converter (VSC) of a distributed generation (DG) unit, as a disturbance signal for islanding detection. The estimated magnitude of the corresponding negative-sequence voltage at the PCC is used as the islanding detection signal. In this paper, based on a laboratory test system, the performance of the islanding detection method under UL1741 anti-islanding test conditions is evaluated. Then, determining the NDZ of the method and proposing the countermeasure, the existence of the NDZ and the performance of the modified method to eliminate the NDZ is verified based on simulation results in PSCAD/EMTDC software environment and experimental tests.
Keywords
power distribution faults; power generation faults; PSCAD/EMTDC software environment; active islanding detection method; distributed generation unit; negative-sequence current; negative-sequence voltage; nondetection zone assessment; voltage-sourced converter; Distributed generation (DG); UL1741 test; islanding detection; microgrid; nondetection zone (NDZ);
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2009.2036016
Filename
5350388
Link To Document