    Grounding faults of cascade battery energy storage system

  • Author

    Ling Zhi-Bin ; Cao Yang ; Ma Qin-Dong ; Chen Man ; Guo Hai-Feng ; Li Yong-Qi

  • Author_Institution
    Electr. Eng. Dept., Shanghai Jiao Tong Univ., Shanghai, China
  • fYear
    2014
  • fDate
    27-31 July 2014
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Grounding faults are inevitable when cascade battery energy storage system (CBESS) is in operation, so the detection and protection are very important in the practical application. The possible grounding fault types of the 10kV CBESS and the detection protection method were analyzed. It could be known that single point grounding fault in CBESS could be detected by monitoring CBESS neutral voltage, and there is no overcurrent in circuit. When two points grounding fault or multi-point grounding fault occurred, the faults could be detected by overcurrent protection or short circuit protection of power unit, and the cascaded battery energy storage system should stop operation.
  • Keywords
    battery storage plants; earthing; energy storage; overcurrent protection; CBESS neutral voltage monitoring; cascade battery energy storage system; detection protection method; grounding fault types; multipoint grounding fault; overcurrent protection; power unit; short circuit protection; voltage 10 kV; Batteries; Circuit faults; Equivalent circuits; Grounding; Inductors; Short-circuit currents; Cascaded Battery energy storage system; Grounding fault; Overcurrent; Power conversion system; Short circuit;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    PES General Meeting | Conference & Exposition, 2014 IEEE
  • Conference_Location
    National Harbor, MD
  • Type

    conf

  • DOI
    10.1109/PESGM.2014.6939330
  • Filename
    6939330