Title :
Investigation of the relationship between ill-conditioned power flow and voltage collapse
Author :
Wang, Y. ; da Silva, L.C.P. ; Xu, Wilsun
Author_Institution :
Dept. of Electr. & Comput. Eng., Alberta Univ., Edmonton, Alta., Canada
fDate :
7/1/2000 12:00:00 AM
Abstract :
Ill-conditioned power flow problems have been widely investigated and discussed in the literature. Typical approaches are to develop enhanced solution algorithms when a power flow case is found to diverge using the conventional Newton method. It is known that a genuine ill-conditioned problem is caused by the presence of a large condition number in the power flow Jacobian matrix. Since a large condition number is associated with small singular values and the voltage collapse is related to small eigenvalues, we therefore speculate that an ill-conditioned power flow problem is actually a voltage collapse problem. The objective of this letter is to demonstrate the relationship between power flow ill conditioning and voltage instability. Case studies of five classical ill-conditioned cases have confirmed that the ill conditioning of power flow indeed occurs-and only occurs-at the voltage collapse point
Keywords :
Jacobian matrices; eigenvalues and eigenfunctions; load flow; power system dynamic stability; conventional Newton method; enhanced solution algorithms; genuine ill-conditioned problem; ill-conditioned power flow; large condition number; power flow Jacobian matrix; small eigenvalues; small singular values; voltage collapse; voltage collapse point; voltage instability; Eigenvalues and eigenfunctions; Jacobian matrices; Load flow; Newton method; Nose; Stability; Voltage;
Journal_Title :
Power Engineering Review, IEEE