DocumentCode :
1354297
Title :
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids Using Phasor Measurement Unit
Author :
Eissa, M.M. ; Masoud, M. Elshahat ; Elanwar, M. Magdy Mohamed
Volume :
25
Issue :
1
fYear :
2010
Firstpage :
270
Lastpage :
278
Abstract :
Current differential protection relays are widely applied to the protection of electrical plant due to their simplicity, sensitivity and stability for internal and external faults. The proposed idea has the feature of unit protection relays to protect large power transmission grids based on phasor measurement units. The principle of the protection scheme depends on comparing positive sequence voltage magnitudes at each bus during fault conditions inside a system protection center to detect the nearest bus to the fault. Then the absolute differences of positive sequence current angles are compared for all lines connecting to this bus to detect the faulted line. The new technique depends on synchronized phasor measuring technology with high speed communication system and time transfer GPS system. The simulation of the interconnecting system is applied on 500 kV Egyptian network using Matlab Simulink. The new technique can successfully distinguish between internal and external faults for interconnected lines. The new protection scheme works as unit protection system for long transmission lines. The time of fault detection is estimated by 5 msec for all fault conditions and the relay is evaluated as a back up relay based on the communication speed for data transferring.
Keywords :
fault location; mathematics computing; power engineering computing; power grids; power system faults; power system measurement; power system protection; power transmission; relay protection; Egyptian network; Matlab Simulink; current differential protection relays; electrical plant protection; external faults; fault detection; internal faults; phasor measurement unit; power transmission grids; unit protection system; voltage 500 kV; wide area protection technique; (GPS) system; Digital protection; discreet Fourier transform; synchronized phasor measurement; time synchronization;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2035394
Filename :
5352313
Link To Document :
بازگشت