• DocumentCode
    135713
  • Title

    A new method for mitigation of power oscillations with fast reclosing of transmission lines based on SIME

  • Author

    Keyvani, B. ; Zadeh, M. Karbalaye ; Lesani, H.

  • Author_Institution
    Sch. of Electr. Eng., Univ. of Tehran, Tehran, Iran
  • fYear
    2014
  • fDate
    27-31 July 2014
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    The high voltage (HV) and Extra High Voltage (EHV) lines could be reestablished by auto-reclosing operation of transmission switches automatically after a certain time from the first tripping during fault. Successful reclosing is carried out considering a dead time which is usually chosen based on the quenching time of possible secondary arc. However, this is not enough to guarantee the transient and dynamic stability of the system. The reclosing instant is the key factor in acceleration or deceleration of power oscillations, and should be determined carefully to ensure the stability of the system. Power oscillations can be mitigated by adaptive selection of the dead time. In this paper, a new method for dead time calculation is proposed in order to mitigate power oscillations effectively. The proposed method is also capable of utilizing in on-line identification because of low amount of calculation required. In this algorithm, single machine infinite bus equivalent (SIME) method is used for evaluation of power oscillations.
  • Keywords
    power system stability; power transmission faults; power transmission lines; EHV lines; HV lines; SIME method; adaptive dead time selection; auto-reclosing operation; dynamic stability; extra high voltage lines; high voltage lines; online identification; power oscillation acceleration; power oscillation deceleration; power oscillation mitigation; quenching time; secondary arc; single machine infinite bus equivalent method; transient stability; transmission line fast reclosing; transmission switches; Acceleration; Oscillators; Power system stability; Rotors; Stability analysis; Transient analysis; SIME; Transmission lines; adaptive reclosing; dead time; power oscillations mitigation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    PES General Meeting | Conference & Exposition, 2014 IEEE
  • Conference_Location
    National Harbor, MD
  • Type

    conf

  • DOI
    10.1109/PESGM.2014.6939542
  • Filename
    6939542