DocumentCode :
1360507
Title :
Use of line surge arresters for the improvement of the lightning performance of 63 kV and 90 kV shielded and unshielded transmission lines
Author :
Sadovic, S. ; Joulie, R. ; Tartier, S. ; Brocard, E.
Volume :
12
Issue :
3
fYear :
1997
fDate :
7/1/1997 12:00:00 AM
Firstpage :
1232
Lastpage :
1240
Abstract :
The lightning performance of 63 kV and 90 kV shielded and unshielded power transmission lines, protected by surge arresters are considered. A specialized software package is used for the computation of the line´s fast front transients. A Monte Carlo statistical method, together with a three-dimensional electrogeometric model is used to determine the lightning stroke locations. Different arrester installation configurations are analyzed and compared. The energy duties of the transmission line surge arresters are computed statistically
Keywords :
Monte Carlo methods; arresters; overvoltage protection; power system analysis computing; power system protection; power system transients; power transmission lines; software packages; 63 kV; 90 kV; Monte Carlo statistical method; computer simulation; energy duties; fast front transients; installation configurations; lightning performance; lightning stroke locations; power transmission line protection; sigma lp software package; surge arresters; three-dimensional electrogeometric model; Arresters; Conductors; Insulation; Lightning; Monte Carlo methods; Poles and towers; Power transmission lines; Statistical analysis; Surge protection; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.636955
Filename :
636955
Link To Document :
بازگشت