DocumentCode :
1360980
Title :
Voltage oscillatory instability caused by induction motor loads
Author :
de Mello, F.P. ; Feltes, J.W.
Author_Institution :
Burnt Hills, NY, USA
Volume :
11
Issue :
3
fYear :
1996
fDate :
8/1/1996 12:00:00 AM
Firstpage :
1279
Lastpage :
1285
Abstract :
Isolated power systems which fit the structure of a single equivalent generator supplying an equivalent composite load can experience a voltage oscillatory instability entirely traceable to the effects of induction motor loads interacting with automatic voltage regulators. This scenario is one where an AVR properly tuned for open circuit conditions is not necessarily well tuned for the on load condition. The phenomenon is explained and a simple solution through AVR compensation is suggested
Keywords :
induction motors; load (electric); oscillations; power system control; power system stability; voltage control; voltage regulators; automatic voltage regulators; equivalent composite load; induction motor loads; isolated power systems; on load condition; open circuit conditions; single equivalent generator; voltage collapse; voltage oscillatory instability; Circuit testing; Impedance; Induction motors; Power generation; Power system dynamics; Regulators; Rotors; Synchronous motors; Voltage; Voltage-controlled oscillators;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.535668
Filename :
535668
Link To Document :
بازگشت