• DocumentCode
    1361190
  • Title

    IEC method of calculation minimum approach distances for live working

  • Author

    Gela, George ; Hotte, Paul W. ; Charest, Marc

  • Author_Institution
    EPRI Power Delivery, Lenox, MA, USA
  • Volume
    15
  • Issue
    2
  • fYear
    2000
  • fDate
    4/1/2000 12:00:00 AM
  • Firstpage
    635
  • Lastpage
    640
  • Abstract
    After 10 years and as many drafts, the proposed IEC standard 61472 is now in the final voting stage. The standard, when published, will define the IEC method of calculating minimum approach distances (MAD) for live working for use worldwide. The standard 61472 provides a method of calculating MAD for voltages between 1 kV and 800 kV AC. In common with other standards, the MAD is taken to consist of two components: an electrical component, DU, and an ergonomic component, DE. The component DU is calculated to minimize the risk of breakdown for all voltages expected at the worksite. The rationale for calculating DU is based on IEC Publications 71-1 and 71-2. The component DE depends on work procedures, training, workers´ skill, type of construction, contingencies such as inadvertent movement and errors in judging distances. Guidelines for selection of DE are included in IEC 61472, but without giving specific values. Atmospheric conditions and specific details of the worksite (such as the effects of broken insulators and electrically floating conductive objects) are counted for through the application of correction factors. Guidelines for selecting the values for these factors are included. This paper provides an overview of the IEC method of calculating MAD, its background and theoretical foundations, and gives comparisons with the IEEE/ESMOL method, which is defined in IEEE Std 516-1995. The paper concentrates on systems voltage levels above 72.5 kV, and on phase-to-ground distances
  • Keywords
    IEC standards; maintenance engineering; power transmission lines; safety; transmission line theory; 1 to 800 kV; IEC calculation method; IEC standard 61472; breakdown risk minimisation; broken insulators; electrical component; electrically floating conductive objects; ergonomic component; guidelines; live working; maintenance personnel safety; minimum approach distances; phase-to-ground distances; Air gaps; Breakdown voltage; Dielectric breakdown; Dielectrics and electrical insulation; Ergonomics; Guidelines; IEC standards; Safety; Standards publication; Voting;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.852997
  • Filename
    852997