Title :
Remote cranking of steam electric stations
Author :
Adibi, M.M. ; Milanicz, D.P. ; Volkmann, T.L.
Author_Institution :
IRD Corp., USA
fDate :
8/1/1996 12:00:00 AM
Abstract :
This paper focuses industry attention on power system restoration. During the initial phase of restoration, black-start combustion turbines are often considered as remote cranking sources for the start-up of steam electric stations. In general, remote cranking operation is carefully planned, simulated and then verified by field tests. This paper describes the planning and simulation used in black-start of two coal-fired generating units utilizing remote combustion turbines. It discusses a number of constraints which have to be considered and simulated in preparation for testing and verification. The paper concludes that, in order to minimize the possibility of damage to equipment during testing or actual restoration, it is necessary to undertake extensive simulation of the procedure. It recommends that the realistic generator reactive capability models be made a part of the network models to allow: optimum selections of tap positions for all the transformers within the remote cranking power system, thus providing adequate lead/lag reactive powers and to maintain acceptable voltage profile while proceeding through various stages of operation
Keywords :
combustion; power system restoration; power transformers; reactive power; starting; steam power stations; steam turbines; auxiliary motors; black-start combustion turbines; coal-fired generating units; equipment damage minimisation; generator reactive capability models; lead/lag reactive powers; power system restoration; remote combustion turbines; remote cranking; start-up; steam electric stations; tap positions; transformers; voltage profile; Combustion; Power generation; Power system modeling; Power system planning; Power system restoration; Power system simulation; Reactive power; Testing; Transformers; Turbines;
Journal_Title :
Power Systems, IEEE Transactions on