• DocumentCode
    1361380
  • Title

    A method for determining customer and utility harmonic contributions at the point of common coupling

  • Author

    Xu, Wilsun ; Liu, Yilu

  • Author_Institution
    Dept. of Electr. Eng., Alberta Univ., Edmonton, Alta., Canada
  • Volume
    15
  • Issue
    2
  • fYear
    2000
  • fDate
    4/1/2000 12:00:00 AM
  • Firstpage
    804
  • Lastpage
    811
  • Abstract
    A new method is proposed in this paper to determine the harmonic contributions of a customer at the point of common coupling. The method can quantify customer and utility responsibilities for limit violations caused by either harmonic source changes or harmonic impedance changes. It can be implemented in current power quality monitors and digital revenue meters. The method makes it possible to develop fair and consistent billing schemes for harmonic distortion control
  • Keywords
    electricity supply industry; harmonic distortion; power supply quality; power system harmonics; billing schemes; customer harmonic contribution; digital revenue meters; harmonic distortion control; harmonic impedance changes; harmonic source changes; limit violations; point of common coupling; power quality monitors; utility harmonic contribution; Environmentally friendly manufacturing techniques; Harmonic distortion; IEC standards; Impedance; Incentive schemes; Industrial pollution; Power quality; Power system harmonics; Reactive power; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.853023
  • Filename
    853023