    Determination of location and amount of series compensation to increase power transfer capability

  • Author

    Rajarman, R. ; Alvarado, Fernando ; Maniaci, Arthur ; Camfield, Robert ; Jalali, Sasan

  • Author_Institution
    Econ. & Eng. Consultants, Lauitis R. Christensen Assoc. Inc., Madison, WI, USA
  • Volume
    13
  • Issue
    2
  • fYear
    1998
  • fDate
    5/1/1998 12:00:00 AM
  • Firstpage
    294
  • Lastpage
    300
  • Abstract
    This paper discusses the merits of an analytical method for determining the location and amount of series compensation to increase the steady state power transfer capability in the power system based primarily on cascading line overload considerations. Steady state transmission limits define the boundaries of a power system operating point. This paper presents tools to identify these boundaries and analytically estimates the change in the boundary limits due to the application of series and shunt compensation. The approach identifies critical lines that can initiate cascading line outages and identifies the optimal location and amount for series compensation. The methodology can also be used to select sites for devices that can extend the availability of power in flowgates
  • Keywords
    compensation; power systems; power transmission; boundary limits; cascading line outages; cascading line overload; power system; power transfer capability; series compensation location; shunt compensation; steady state power transfer capability; steady state transmission limits; Costs; Power generation; Power generation economics; Power system analysis computing; Power system economics; Power system planning; Power system reliability; Power systems; Space technology; Steady-state;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.667338
  • Filename
    667338