Title :
Analysis on the control principle of the active DC filter in the Lindome converter station of the Konti-Skan HVDC link
Author :
Zhang, Wenyan ; Isaksson, Alf J. ; Ekström, Åke
Author_Institution :
HVDC Div., ABB Power Syst. Inc., Ludvika, Sweden
fDate :
5/1/1998 12:00:00 AM
Abstract :
The control principle of a hybrid passive-active DC filter installed in the Lindome HVDC converter station is analyzed in this paper. The controller of the active filter includes two basic functions: an integrator and a compensator. The main advantage of the Lindome controller is its simple structure for implementation in a digital signal processor (DSP). The drawbacks of this controller are its long response time, low stability margin and the filtering of an unnecessary number of frequencies. An alternative control strategy using a number of notch filters has been investigated. The notch filters can be tuned to those frequencies that need to be damped. This controller gives a much shorter system response time and improved stability margin
Keywords :
HVDC power convertors; HVDC power transmission; active filters; control system analysis; notch filters; power filters; power system control; substations; HVDC converter station; Konti-Skan HVDC link; active DC filter; compensator; control principle; digital signal processor; integrator; notch filters; response time; stability margin; Active filters; Coils; Control systems; Filtering; HVDC transmission; Magnetic field measurement; Passive filters; Power harmonic filters; Power system harmonics; Voltage control;
Journal_Title :
Power Systems, IEEE Transactions on