Harmonic Distortion Influence on Grounded Wye Shunt Capacitor Banks Protection: Experimental Results
Author :
Santos, H.L. ; Paulino, Jose Osvaldo S. ; Boaventura, Wallace C. ; Baccarini, Lane Maria Rabelo ; Murta, M.L.
Author_Institution :
Fed. Univ. of Minas Gerais, Belo Horizonte, Brazil
Volume :
28
Issue :
3
fYear :
2013
fDate :
Jul-13
Firstpage :
1289
Lastpage :
1296
Abstract :
The increase of harmonic current circulation in electric system affects the shunt capacitor banks protection arrangement, causing false alarms and trips and leading to a reduction of the relay sensitivity. This paper analyzes the behavior of the protection system on a reduced-scale model, which reproduces the main features of grounded wye shunt capacitor banks. In such experiments, high levels of current harmonic distortion, voltage unbalance, and bank inherent unbalance were considered. This paper brings experimental analyses for protection arrangements considering robustness and sensitivity.
Keywords :
power capacitors; power system harmonics; power system protection; bank inherent unbalance; electric system; grounded wye shunt capacitor banks protection; harmonic current circulation; harmonic distortion; protection system; voltage unbalance; Capacitance; Capacitors; Current measurement; Harmonic analysis; Relays; Sensitivity; Voltage measurement; Capacitor banks protection; harmonic distortion; protection sensitivity;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2013.2253805
Filename :
6495732
Link To Document :
بازگشت