Title :
Harmonic Distortion Influence on Grounded Wye Shunt Capacitor Banks Protection: Experimental Results
Author :
Santos, H.L. ; Paulino, Jose Osvaldo S. ; Boaventura, Wallace C. ; Baccarini, Lane Maria Rabelo ; Murta, M.L.
Author_Institution :
Fed. Univ. of Minas Gerais, Belo Horizonte, Brazil
Abstract :
The increase of harmonic current circulation in electric system affects the shunt capacitor banks protection arrangement, causing false alarms and trips and leading to a reduction of the relay sensitivity. This paper analyzes the behavior of the protection system on a reduced-scale model, which reproduces the main features of grounded wye shunt capacitor banks. In such experiments, high levels of current harmonic distortion, voltage unbalance, and bank inherent unbalance were considered. This paper brings experimental analyses for protection arrangements considering robustness and sensitivity.
Keywords :
power capacitors; power system harmonics; power system protection; bank inherent unbalance; electric system; grounded wye shunt capacitor banks protection; harmonic current circulation; harmonic distortion; protection system; voltage unbalance; Capacitance; Capacitors; Current measurement; Harmonic analysis; Relays; Sensitivity; Voltage measurement; Capacitor banks protection; harmonic distortion; protection sensitivity;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2013.2253805