DocumentCode
1363311
Title
Survey of harmonic voltage and current at distribution substation in Northern Taiwan
Author
Hu, Chung-Hsing ; Wu, Chi-Jui ; Yen, Shih-Shong ; Chen, Yun-Wu ; Wu, Bor-An ; Hwang, Jan-San
Author_Institution
Nat. Taiwan Inst. of Technol., Taipei, Taiwan
Volume
12
Issue
3
fYear
1997
fDate
7/1/1997 12:00:00 AM
Firstpage
1275
Lastpage
1284
Abstract
This paper presents a survey of voltage and current harmonic distortion levels at 40 power transformers and 10 power capacitor units in Northern Taiwan. Through one year of measurements, about 12,000 sets of harmonic voltage and current data were recorded and analyzed. The types and levels of harmonics are shown in each power transformer which supplies different residential, commercial and industrial customers with various loads. At the same time, a suggestion is given to the representative value of the background level of harmonic voltages with 95% cumulative probability which is adopted by Taipower. In conclusion, the effects of harmonics on capacitors and power transformers are discussed
Keywords
distribution networks; harmonic distortion; power capacitors; power supply quality; power system harmonics; power transformers; probability; substations; transformer substations; Northern Taiwan; cumulative probability; distribution substation; harmonic currents; harmonic distortion levels; harmonic voltages; power capacitor; power transformer; Current measurement; Distortion measurement; Electrical equipment industry; Harmonic analysis; Harmonic distortion; Power capacitors; Power system harmonics; Power transformers; Substations; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.637004
Filename
637004
Link To Document