DocumentCode :
1364568
Title :
An Accurate Time-Domain Procedure for Harmonics and Interharmonics Detection
Author :
Chang, Gary W. ; Chen, Cheng-I
Author_Institution :
Dept. of Electr. Eng., Nat. Chung Cheng Univ., Chiayi, Taiwan
Volume :
25
Issue :
3
fYear :
2010
fDate :
7/1/2010 12:00:00 AM
Firstpage :
1787
Lastpage :
1795
Abstract :
Frequency is an important indicator for the quality of electric power. Accurate spectral decompositions rely much on the correct identification of frequencies of the measured signals. An efficient procedure that includes a high-resolution Prony-based method in conjunction with the downsampling technique for harmonics and interharmonics detection of the measured power signal is proposed in this paper. It is shown that even when two or more closely adjacent spectral lines are present, the proposed method can precisely detect the harmonic and interharmonic components. The performance of the proposed method is validated by testing the simulated and actual measured power signals. Results are compared with those obtained by fast Fourier transform with and without synchronization, IEC subgrouping method, and other commonly used linear prediction approaches adopted in the Prony´s method. It shows that the proposed method is more accurate on the detection of harmonics and interharmonics with high resolution.
Keywords :
fast Fourier transforms; power supply quality; power system harmonics; synchronisation; IEC subgrouping method; adjacent spectral lines; downsampling technique; electric power quality; fast Fourier transform; high-resolution Prony-based method; interharmonics detection; linear prediction; spectral decompositions; synchronization; time-domain procedure; Downsampling; Prony´s method; harmonics; interharmonics; singular value decomposition (SVD);
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2037230
Filename :
5361340
Link To Document :
بازگشت