DocumentCode :
1368951
Title :
Reactive power reduction in three-phase electric arc furnace
Author :
Wolf, Albrecht ; Thamodharan, Manoharan
Author_Institution :
Inst. of Electr. Power Eng., Tech. Univ. Clausthal, Germany
Volume :
47
Issue :
4
fYear :
2000
fDate :
8/1/2000 12:00:00 AM
Firstpage :
729
Lastpage :
733
Abstract :
A conventional three-phase electric arc furnace causes flicker at the point of common coupling with AC mains. This generally occurs with AC mains having a low short-circuit capacity. The flicker is caused by flucluating reactive power consumption of the furnace. This paper describes a way, through computer simulation, of increasing the dynamic performance of the furnace and keeping reactive power consumption constant. This can be achieved with the addition of a three-phase power controller and a booster transformer to the power source and the introduction of a new control method of regulating the reactive power input. The problem of flicker can thus be minimized. This was experimentally tested on a single-phase model and the results obtained were very satisfying. Due to laboratory facilities, the three-phase testing was not performed
Keywords :
arc furnaces; digital simulation; power consumption; power engineering computing; power transformers; reactive power control; AC mains; booster transformer; computer simulation; control method; dynamic performance improvement; flicker; flucluating reactive power consumption; low short-circuit capacity; point of common coupling; reactive power input regulation; reactive power reduction; single-phase model; three-phase electric arc furnace; three-phase power controller; Admittance; Circuit breakers; Circuit testing; Computer simulation; Electric resistance; Furnaces; Reactive power; Reactive power control; Switches; Voltage;
fLanguage :
English
Journal_Title :
Industrial Electronics, IEEE Transactions on
Publisher :
ieee
ISSN :
0278-0046
Type :
jour
DOI :
10.1109/41.857952
Filename :
857952
Link To Document :
بازگشت