    New England Electric´s 39 years of experience with resonant neutral grounding of unit-connected generators

  • Author

    Gulachenski, E.M. ; Courville, E.W.

  • Author_Institution
    New England Power Service Co., Westborough, MA, USA
  • Volume
    6
  • Issue
    3
  • fYear
    1991
  • fDate
    7/1/1991 12:00:00 AM
  • Firstpage
    1016
  • Lastpage
    1024
  • Abstract
    Since 1951 all unit connected generators of the New England Electric System Companies have been grounded using ground fault neutralizers (GFNs). This grounding method permits protection against phase-to-ground faults on the generator bus that is more sensitive than with resistor grounded units. In addition, the fault current is limited to such a low value that the possibility of stator iron burning is practically eliminated. Also, because of the limited fault current, overvoltage due to arcing is not possible. These advantages of ground-fault neutralizer generator protection are illustrated through discussion of actual operating experience and by calculations for a typical generator
  • Keywords
    earthing; electric generators; electrical faults; New England Electric; ground fault neutralizers; limited fault current; phase-to-ground faults; resonant neutral grounding; unit-connected generators; Circuit faults; Fault currents; Fault detection; Grounding; Inductors; Protection; Protective relaying; Resistors; Resonance; Voltage control;