DocumentCode
1369457
Title
Field test results for a multi-shot 12.47 kV fault current limiter
Author
Engelman, Neil ; Schreurs, Emile ; Drugge, Birger
Author_Institution
Lincoln Electr. Syst., NE, USA
Volume
6
Issue
3
fYear
1991
fDate
7/1/1991 12:00:00 AM
Firstpage
1081
Lastpage
1087
Abstract
During ten months of 1989, a prototype multishot 12.47 kV fault current limiter (FCL) was installed in a field test mode at a simulation in Lincoln, Nebraska. The authors present the principles of operation, computer simulations, and the results of the field test. Nineteen fault occurrences were successfully handled by the FCL. Examples of actual faults include currents of 3900 A reduced to 2140 A and bus voltage sags improved from 0.33 to 0.9 per unit. The FCL features tested and proven in this field test were the dynamic insertion of the resistive rail to limit the first one half cycle of fault current without causing voltage or current transients, limiting the remaining cycles of fault current with the limiting resistor, automatic resetting of the device during current zero, and the large continuous current rating with no additional losses
Keywords
digital simulation; fault currents; limiters; power engineering computing; testing; 12.47 kV; Lincoln; Nebraska; automatic resetting; bus voltage sags; computer simulations; current zero; field test mode; limiting resistor; multishot fault current limiter; resistive rail; Automatic testing; Computational modeling; Computer simulation; Fault current limiters; Fault currents; Power quality; Rails; Resistors; Virtual prototyping; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.85851
Filename
85851
Link To Document