Title :
Principal decomposition by-products generated at various abnormalities in gas-insulated transformers
Author :
Mukaiyama, Y. ; Takagi, I. ; Ishihara, H. ; Kudo, A. ; Makino, Y. ; Hosokawa, N.
Author_Institution :
Chubu Electr. Co. Inc., Nagoya, Japan
fDate :
7/1/1991 12:00:00 AM
Abstract :
It is pointed out that the application of decomposition gas analysis based on GC and IC (gas and ion chromatography) methods provides a promising practical means of predictive diagnosis of gas-insulated transformers. As the first step of developing a diagnostic method, model tests simulating important modes of abnormalities in a gas-insulated transformer were carried out. Major components characteristic of each abnormality such as SO2 in the case of metal overheat and SO2F2 in the case of partial discharges were identified by the experiments. Attention is also paid to the effect of material differences, which is a major factor differentiating the gas-insulated transformer from other gas-insulated apparatus
Keywords :
chromatography; gaseous insulation; power transformers; SO2; SO2F2; decomposition by-products; gas chromatography; gas-insulated transformers; ion chromatography; metal overheat; partial discharges; Building materials; Copper; Gas insulation; Inorganic materials; Insulation testing; Positron emission tomography; Silicon; Steel; Transformers; Water heating;
Journal_Title :
Power Delivery, IEEE Transactions on