DocumentCode
1369577
Title
Calculation and measurement of field parameters during live-line maintenance
Author
Yan, Z. ; Qin, B.L. ; Lin, X. ; Weng, R.Y. ; Gela, G.
Author_Institution
Xian Jiaotong Univ., China
Volume
6
Issue
3
fYear
1991
fDate
7/1/1991 12:00:00 AM
Firstpage
1187
Lastpage
1195
Abstract
The authors discuss the application of the charge simulation method (CSM) for calculation of the electric field and induced currents during live-line maintenance operations on a 330 kV line using insulating ladders. Several cases are considered, including the effect of orientation of the ladder and situations with damaged suspension insulators. Calculated field quantities include the electric field strengths and currents induced in the worker´s body. The CSM described can include cases with floating electrodes (insulator caps). The calculated results for field values along the ladder are still sufficiently accurate even when many insulators in a string are damaged. The engineering accuracy of the computational method was demonstrated through comparisons with measured data, determined using a small field probe. Results obtained are useful in identifying situations which may not be sufficiently safe for conducting live-line maintenance
Keywords
electric field measurement; insulators; maintenance engineering; power overhead lines; 330 kV; body currents; charge simulation method; damaged suspension insulators; electric field; floating electrodes; induced currents; insulating ladders; insulator caps; live-line maintenance; Conductors; Data engineering; Dielectrics and electrical insulation; Electrical safety; Electrodes; Poles and towers; Power distribution; Power engineering and energy; Power measurement; Transmission line measurements;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.85867
Filename
85867