Title :
Influence of contact resistance on shielding efficiency of shielding gutters for high-voltage cables
Author :
Koroglu, S. ; Sergeant, Peter ; Sabariego, Ruth V. ; Dang, V.Q. ; De Wulf, M.
Author_Institution :
Dept. of Electr. & Electron. Eng., Pamukkale Univ., Denizli, Turkey
fDate :
11/1/2011 12:00:00 AM
Abstract :
The shielding of buried three-phase high-voltage power lines can be done by placing them in conducting ferromagnetic U-shaped gutters covered with plates. In case of a perfect electrical contact between adjacent gutters and between adjacent cover plates, induced currents in the shield efficiently reduce the magnetic field generated by the cables. As however a perfect contact cannot be guaranteed, in practice, it is useful to quantify the effect of a defective electrical contact on the field reduction. From two-dimensional/three-dimensional finite element computations and experiments, the influence of the contact resistance on the shielding efficiency is investigated, as a function of the ratio of axial length to height of the shield elements. Furthermore, the effect of other parameters on the shielding efficiency is studied: the ratio of axial length to height, a parasitic air gap between the gutter and the cover plate and the type of the shield material. It was found that a low contact resistance deteriorates much more the shielding in case of an aluminium shield than in case of a steel shield. As expected, the effect is larger for shield elements with relatively short axial length with regard to the other dimensions. Nevertheless, the effect remains quite significant for aluminium shields with practically convenient dimensions.
Keywords :
air gaps; cable shielding; contact resistance; electrical contacts; finite element analysis; power cables; adjacent cover plates; axial length ratio; buried three-phase high-voltage power lines; contact resistance; ferromagnetic U-shaped gutters; field reduction; high-voltage cables; magnetic field; parasitic air gap; perfect electrical contact; shielding gutter efficiency; two-dimensional-three-dimensional finite element computations;
Journal_Title :
Electric Power Applications, IET
DOI :
10.1049/iet-epa.2011.0081