DocumentCode :
1371545
Title :
Power quality measurements performed on a low-voltage grid equipped with two wind turbines
Author :
Thiringer, Torbjörn
Author_Institution :
Dept. of Electr. Power Electron., Chalmers Univ. of Technol., Goteborg, Sweden
Volume :
11
Issue :
3
fYear :
1996
fDate :
9/1/1996 12:00:00 AM
Firstpage :
601
Lastpage :
606
Abstract :
The power quality of a low-voltage grid with two wind turbines is investigated. Slow voltage variations as well as transients and harmonics are measured and analysed. Furthermore, the spectrum of the power is determined so that the presence of periodic power components can be investigated. Although periodic power fluctuations reaching 10% of the rated power are registered, voltage variations are lower than the prescribed IEC flicker limit at steady-state operation. As the turbines are put on-line, the voltage level is lowered by 3%, which exceeds the flicker limit. The risk for flicker increases if the X/R ratio of the grid is low and if turbines which have a tendency to produce large periodic power fluctuations are used
Keywords :
distribution networks; power measurement; power supply quality; power system harmonics; power system measurement; power system transients; wind turbines; flicker limit; harmonics; low X/R ratio; low-voltage grid; periodic power fluctuations; power quality measurements; slow voltage variations; steady-state operation; transients; two wind turbines; variable speed systems; voltage variations; Blades; Inductance; Performance evaluation; Poles and towers; Power measurement; Power quality; Voltage fluctuations; Wind energy generation; Wind speed; Wind turbines;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.537031
Filename :
537031
Link To Document :
بازگشت