DocumentCode :
1372238
Title :
Ampacity Calculation for DLO Cable Used in Permanent Installations
Author :
Cardinal, Paul G.
Author_Institution :
Shell Exploration & Production, Houston, TX, USA
Volume :
47
Issue :
1
fYear :
2011
Firstpage :
281
Lastpage :
285
Abstract :
DLO is a railroad industry designation given to flexible cables certified for use in diesel locomotives. For use outside the railroad industry, these cables may be labeled with a UL insulation-type certification such as RHW-2. Carried over from the cables´ railroad lineage are sizes such as 535 kcmil that are absent from NEC tables. While interpolation of NEC tables may appear as a logical means of calculating ampacity, the NEC limits ampacity calculation options to the formula provided in 310.15(C). Applications of the 310.15(C) formula for cables in underground duct banks are well documented, but constants for duplicating conditions of NEC Table 310.16 are absent from the NEC. For application of nonstandard cable sizes in conditions matching those of NEC Table 310.16, this paper provides ampacity calculations while also clarifying the delineation between permanent building wiring and temporary cords as defined by the NEC.
Keywords :
diesel-electric locomotives; electric conduits; interpolation; power cable insulation; railway industry; DLO cable; NEC tables; UL insulation-type certification; ampacity calculation; diesel locomotives; interpolation; permanent building wiring; permanent installations; railroad industry; temporary cords; underground duct banks; Cable insulation; Cable shielding; Conductors; Thermal conductivity; Thermal resistance; Wires; Ampacity; DLO; cable; calculation; flexible; generator;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.2010.2091379
Filename :
5624578
Link To Document :
بازگشت