• DocumentCode
    1374213
  • Title

    “Right sizing” circuit breakers in motor starters

  • Author

    Padden, Lorraine K. ; Gregory, George D.

  • Author_Institution
    Padden Eng., Katy, TX, USA
  • Volume
    6
  • Issue
    5
  • fYear
    2000
  • Firstpage
    23
  • Lastpage
    32
  • Abstract
    Instantaneous-trip, molded-case circuit breakers (MCCBs) have been applied successfully for low-voltage motor protection for many years. However, the changes in motor-starting characteristics have created more difficult challenges for the application engineer. The major challenge is successfully starting the low-voltage motor without causing the instantaneous-trip breaker to falsely trip without exceeding equipment ratings or violating limitations in the National Electrical Code (NEC). "Right sizing" circuit breakers for use in low-voltage combination motor starters is critical to the successful, reliable operation of plant and process facilities. If not properly applied, false tripping on motor starting and contact welding of contactors may occur. Moreover, changes in the NEC and improved motor efficiencies have impacted equipment selection and protection. The following information is intended to guide application engineers in their selection of the right breaker and its setting for more reliable motor protection: combination motor-starter components, circuit breaker characteristics, circuit breaker and combination. starter testing, motor starting characteristics, and component selection using coordination examples. The examples show how selecting the right breaker and breaker setting can avoid false tripping during starting, mitigate contact welding, and provide backup protection for overload conditions
  • Keywords
    circuit breakers; electric motors; motor protection; starting; National Electrical Code; backup protection; circuit breaker characteristics; combination motor-starter components; component selection; contact welding; contactors; false tripping; instantaneous-trip molded-case circuit breakers; low-voltage combination motor starters; low-voltage motor protection; motor efficiencies; motor starters; motor starting characteristics; overload conditions; right sizing circuit breakers; Circuit breakers; Energy efficiency; Motor drives; National electric code; Protection; Protective relaying; Relays; Rotors; Switches; Voltage;
  • fLanguage
    English
  • Journal_Title
    Industry Applications Magazine, IEEE
  • Publisher
    ieee
  • ISSN
    1077-2618
  • Type

    jour

  • DOI
    10.1109/2943.863632