DocumentCode
1376535
Title
The elimination of motor-generator sets as transient buffers for SAGE computers
Author
Gano, J. J.
Author_Institution
Lincoln Laboratory, Massachusetts Institute of Technology, Lexington, Mass.
Volume
76
Issue
4
fYear
1957
Firstpage
468
Lastpage
473
Abstract
Motor-generator sets are frequently used as buffers to isolate electronic equipment from severe power transients which may cause misoperation. An investigation of voltage tolerances for digital computers, performance of d-c supplies, and probabilities of fault occurrences indicates that if the power is generated on the site of the electronic equipment, motor-generator sets are not necessary to meet the critical requirements of the digital computers employed in the SAGE (Semi-Automatic Ground Environment) air-defense system.
Keywords
Circuit faults; Computer errors; Computers; Generators; Power cables; Transient analysis;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Part I: Communication and Electronics, Transactions of the
Publisher
ieee
ISSN
0097-2452
Type
jour
DOI
10.1109/TCE.1957.6372325
Filename
6372325
Link To Document