• DocumentCode
    1376535
  • Title

    The elimination of motor-generator sets as transient buffers for SAGE computers

  • Author

    Gano, J. J.

  • Author_Institution
    Lincoln Laboratory, Massachusetts Institute of Technology, Lexington, Mass.
  • Volume
    76
  • Issue
    4
  • fYear
    1957
  • Firstpage
    468
  • Lastpage
    473
  • Abstract
    Motor-generator sets are frequently used as buffers to isolate electronic equipment from severe power transients which may cause misoperation. An investigation of voltage tolerances for digital computers, performance of d-c supplies, and probabilities of fault occurrences indicates that if the power is generated on the site of the electronic equipment, motor-generator sets are not necessary to meet the critical requirements of the digital computers employed in the SAGE (Semi-Automatic Ground Environment) air-defense system.
  • Keywords
    Circuit faults; Computer errors; Computers; Generators; Power cables; Transient analysis;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Part I: Communication and Electronics, Transactions of the
  • Publisher
    ieee
  • ISSN
    0097-2452
  • Type

    jour

  • DOI
    10.1109/TCE.1957.6372325
  • Filename
    6372325