Abstract
An interruption method for low-voltage, small-capacity, air-break contactors is developed. The features of the construction of this method are that a slit is formed in the stationary conductor with a contact, and an arc runner is located on the slit. The operation, construction, experimental conditions and results, and applications of the method are discussed. The method shortens the maximum arcing time in a 726 V, 74 A circuit by about 70% and reduces contact wear in a 440 V, 80 A circuit by 21%, compared with the conventional method. This method produces enough magnetic flux density to drive an arc. The shortening of the maximum arcing time and reduction of the contact wear are considered to be due to the electromagnetic drive of the arc. This method has been applied to contactors of 18 A and 21 A frames; it increased their rated operational current for AC3 duty at 660 V by 50%
Keywords
contactors; 440 V; 726 V; 74 A; 80 A; AC3 duty; LV air-break contactors; arc runner; contact wear; electromagnetic drive; interruption method; magnetic flux density; maximum arcing time; rated operational current; Bridges; Conductors; Contactors; Costs; Electromagnetic analysis; Industry Applications Society; Magnetic fields; Solid state circuits; Switching circuits; Vacuum arcs;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.67548
Filename
67548
Link To Document