DocumentCode :
1379405
Title :
Electric breakdown of transformer oil
Author :
Watson, P.K. ; Higham, J.B.
Author_Institution :
English Electric Co., Ltd., Stafford, UK
Volume :
100
Issue :
3
fYear :
1953
fDate :
3/1/1953 12:00:00 AM
Firstpage :
168
Lastpage :
174
Abstract :
A research programme has been commenced which is designed to determine the mechanisms of electric breakdown in insulating liquids under various conditions. The paper describes experimental equipment and techniques, and some results which have been obtained on transformer oil. Special equipment includes a transparent pressure chamber with an internal glass test-vessel, which enables the liquid under test to be subjected to hydrostatic pressures up to 500 lb/in2 and voltages up to 100 kV peak. A protective circuit hasbeen developed, incorporating triggered spark-gap, which limits the duration of breakdown currents to a few microseconds. A wide range of breakdown strengths has been obtained, varying from 5 000 kVpeak/cm with 1-microsec impulses, to below 100 kV(r.m.s.)/cm for a fibre contaminated oil under a.c. test conditions. The removal of fibres raises the a.c. strength of otherwise untreated oil to 400 kV(r.m.s.)/cm. It is concluded that a breakdown mechanism initiated by cavitation is operative in certain circumstances.
Keywords :
electric breakdown; transformer oil;
fLanguage :
English
Journal_Title :
Proceedings of the IEE - Part IIA: Insulating Materials
Publisher :
iet
Type :
jour
DOI :
10.1049/pi-2a.1953.0027
Filename :
5240727
Link To Document :
بازگشت