DocumentCode
1387606
Title
A busbar protection technique and its performance during CT saturation and CT ratio-mismatch
Author
Sachdev, Mohindar S. ; Sidhu, Tarlochan S. ; Gill, Harjeet Singh
Author_Institution
Power Syst. Res. Group, Saskatchewan Univ., Saskatoon, Sask., Canada
Volume
15
Issue
3
fYear
2000
fDate
7/1/2000 12:00:00 AM
Firstpage
895
Lastpage
901
Abstract
This paper describes a digital technique for protecting busbars. The technique uses positive- and negative-sequence models of the power system in a fault-detection algorithm. While phase voltages and currents are used to detect faults, parameters of the power system are not used. An analysis of the performance of the proposed technique during CT saturation and ratio-mismatch conditions is presented. The performance of the technique was investigated for a variety of operating conditions and for several busbar configurations. Data generated by EMTP simulations of model power systems were used in the investigations. The results indicate that the proposed technique is stable during CT saturation and ratio-mismatch conditions
Keywords
EMTP; busbars; current transformers; fault location; microcomputer applications; power system protection; relay protection; EMTP simulations; busbar configurations; busbar protection technique; current transformer ratio-mismatch; current transformer saturation; digital technique; fault-detection algorithm; negative-sequence models; operating conditions; phase currents; phase voltages; positive-sequence models; power system; symmetrical components; Circuit faults; Electrical fault detection; Fault currents; Fault detection; Power system analysis computing; Power system faults; Power system modeling; Power system protection; Power system simulation; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.871349
Filename
871349
Link To Document