DocumentCode :
1387654
Title :
A study of current-carrying capacity of drawlead cable in condenser bushing
Author :
Zeng, Daxiong
Author_Institution :
Lapp Insulator Co., LeRoy, NY, USA
Volume :
15
Issue :
3
fYear :
2000
fDate :
7/1/2000 12:00:00 AM
Firstpage :
925
Lastpage :
930
Abstract :
Temperature rise distribution at the drawlead cables in the condenser bushings was studied with a thermal model and actual thermal tests. Temperature rise of the hottest spot at the cables from the model is consistent with that from the tests within a 10% deviation. Factors that influence working current and overload capacity of the cable were studied. Current-carrying capacities of the drawlead cables with index 105 insulation are presented based on thermal basis of rating
Keywords :
bushings; power cable testing; power capacitors; temperature distribution; temperature measurement; thermal analysis; condenser bushing; current-carrying capacities; current-carrying capacity; drawlead cable; hot spot temperature rise; index 105 insulation; overload capacity; temperature rise distribution; thermal model; thermal tests; working current; Cable insulation; Insulators; Petroleum; Power cable insulation; Power cables; Resistance heating; Temperature; Testing; Thermal conductivity; Thermal resistance;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.871354
Filename :
871354
Link To Document :